How far from a transformer can arresters be located yet still ensure an adequate margin of protection? As explained by Jonathan Woodworth in this edited contribution to INMR, the answer is seldom simple. One rule of thumb is: locate the arrester as close to the transformer bushing as possible. Indeed, this is what is usually recommended, although it is not always feasible, especially at higher system voltages.

hv-Arrester

hv-Arrester-1

hv-Arrester-2

Fig. 1: Examples of arrester-transformer configuration at substations.

At voltages of 400 kV and higher, arresters can become too large to be easily supported by the transformer’s body and must be mounted on separate structures and pedestals. Such ‘extended’ separation distance is also needed in cases where transformers have to be easily moved for repair. For example, access roads for this purpose can sometimes result in up to 30 m of separation of arrester from transformer.

Unfortunately, separation distance (or protective zone) of this magnitude can result in reduced protection when a fast rising surge enters the station from an overhead line at nearly the speed of light. When the surge hits the arrester, voltage is indeed reduced – but not to zero and, at best, to the discharge voltage of the arrester. The resulting surge traveling past the arrester is reflected at the transformer, which can result in voltage doubling if the separation distance is sufficiently great. While in most cases reflected voltage only increases incoming surge by a few percent, it is this traveling wave phenomenon and the associated reflection factor that highlight the importance of separation distance.

Help was offered in IEEE’s Application Guide on Arresters C62.22 and also in IEC 60099-5. In C62.22, a formula determines the maximum distance at which an arrester can be mounted yet still achieve a protection margin of 15%. To illustrate how this formula works in graphical terms using a transient program (ATP), below are simulation results for a substation with arresters located 1m (Fig. 2), 15m (Fig. 3) and 30m (Fig. 4) from 500 kV transformer bushings. All other parameters remain the same and these numbers were chosen only to demonstrate simple insulation coordination in a substation. The arresters are mounted on a pedestal that results in 5m from earth ground to the base with their tops located 1m from the incoming line.

As shown in Fig. 2, the voltages at the arrester and transformer are, as expected, identical and peak at 1326 kV. This leaves a margin of protection of 16% for a 1550 kV BIL transformer, which is the minimum recommended according to IEC and IEEE. The simulation in Fig. 3, with 15m distance between arrester and transformer bushing, sees margin of protection reduced to only 8%, which is less than recommended but still not above the transformer’s BIL of 1550 kV.

Transient-voltages-at-substation-with-separation-distance-of-1m

Fig. 2: Transient voltages at substation with separation distance of 1m.

Transient-voltages-at-substation-with-separation-distance-of-15m

Fig. 3: Transient voltages at substation with separation distance of 15m.

Transient-voltages-at-substation-with-separation-distance-of-30m

Fig. 4: Transient voltages at substation with separation distance of 30m.

Fig. 4 makes it clear that 30m separation distance would result in the voltage at the transformer exceeding its withstand level (BIL), meaning that a fast rising surge entering the station in such a case could cause serious damage. Therefore, if for whatever reason it became necessary for the arrester to be located 30m from the bushing, a transformer with higher withstand (BIL) would have to be specified.


This article is copy from INMR (https://www.inmr.com),Not for commercial use, only for technical learning and communication.

Table of Content list

RELATED NEWS

content is empty!

PRODUCT

QUICK LINKS

CONTACT US

Email:  jonsonchai@chinahaivo.com

             sales@chinahaivo.com

             54442019@qq.com

Wechat:+86 13587716869

WhatsApp:+86 13587716869

Tel:       0086-577-62836929

              0086-577-62836926

              0086-13587716869

              0086-15957720101

Get Touch With Us

Contact us

If you have any questions, you can contact us through the form.

Copyright © 2020 Haivo Electrical Co.,Ltd Support  by  leadong.com   Sitemap  |  Privacy Policy