High-voltage Isolator is a critical component in electrical power systems, designed to physically isolate sections of a circuit to ensure safety during maintenance, repairs, or system reconfiguration. Unlike circuit breakers, disconnectors are not intended to interrupt load currents or fault currents. Instead, they provide a visible break in the circuit, confirming de-energization for personnel safety.
Isolator are used to isolate de-energized equipment (e.g., transformers, circuit breakers, or transmission lines) from live high-voltage circuits. This ensures safe working conditions for maintenance crews.
They enable switching between different power system configurations, such as rerouting power flow or connecting/disconnecting backup lines.
Isolator work in tandem with circuit breakers. While the breaker interrupts current, Isolator provides physical isolation once the circuit is de-energized.
The mechanical separation of contacts creates a visible air gap, confirming that no voltage is present on the isolated section.
In ultra-high-voltage (UHV) systems, disconnectors may assist in managing voltage distribution across insulators.
A high-voltage disconnector operates based on mechanical separation of contacts to create an isolating gap. Key components include:
Fixed Contact: Mounted on the stationary part of the disconnector.
Moving Contact: Attached to an insulating arm, which is rotated or slid open/closed by an operating mechanism.
Porcelain or composite insulators provide electrical insulation between live parts and the grounded structure.
Manual, motorized, or pneumatic systems drive the movement of the contacts.
When activated, the moving contact separates from the fixed contact, creating an air gap. This action is performed only after the circuit breaker has interrupted the current.
The gap must withstand the system’s rated voltage without arcing.
The moving contact re-engages with the fixed contact to restore the electrical path. Closing is done under no-load conditions or after confirming synchronization in ring main systems.
Arc Resistance: Contacts are designed to avoid arcing during operation (used only in a de-energized state).
Corona Control: Smooth geometries minimize corona discharge in high-voltage applications.
Mechanical Stability: Robust construction ensures reliability under environmental stress (wind, ice, seismic activity).
High-voltage disconnectors comply with international standards such as IEC 62271-1 and IEEE C37.32, which define performance criteria for dielectric strength, mechanical endurance, and environmental resilience.
High-voltage disconnectors are indispensable for ensuring safety and operational flexibility in power systems. By providing a reliable physical isolation point, they protect personnel and equipment, enabling efficient maintenance and system management in transmission and distribution networks. Their design prioritizes simplicity, durability, and compliance with stringent electrical safety standards.