11-15kv Fuse Links for Expulsion Fuse Cutout
Home » Products » Fuse » Fuse links for expulsion fuse cutout » 11-15kv Fuse Links for Expulsion Fuse Cutout

loading

Share to:
sharethis sharing button

11-15kv Fuse Links for Expulsion Fuse Cutout

Availability:
  • type K

  • HAIVOL

HAIVOL brand type K, type T, type H and type SLOW-FAST fuse link manufacture and test according to the latest international standard IEC 60282-2:2008 & IEEE Std C37.41-2008 & IEEE Std C37.42-2009.

1. Fusible element adopts the material of silver-copper alloy.Using precision technology and strict testing to guarantee accurate characteristics of time-current.

2. Fusible element be crimping to fasten cable wire,and fixed by high strength strain wire.That guarantee excellent mechanical strength.It will not be affected,even if under external factors such as vibration and high current impact.

3. The Arc extinguishing tube has excellent performance of arc extinguishing when low current overload fault.

4. We also supply Type K and Type T twin pigtails fuse link, The twin pigtails fuse link is convenient and easier to install in the fuse cutout than conventional single pigtail fuse links. The twin pigtails attach under the attachment stud on each side separately.


上

下

Type Slofast Fuse Links

Amps

Diameter of buttonhead mm

Size of arc extinguishing tube mm


0.4Amp

0.6Amp

0.7Amp

1.0Amp

1.3Amp

1.4Amp

1.6Amp

2.1Amp

3.1Amp

3.5Amp

4.2Amp

5.2Amp

6.3Amp

7.0Amp

7.8Amp

10.4Amp

14Amp

21Amp

32Amp


∅12.50 ∅8.0*130
46Amp ∅19.00 ∅10.0*130


11-15kv Fuse link length 21'(533mm)     
24-27kv Fuse link length 23'(584mm)     
33-38kv Fuse link length 31'(787mm)

Type K Fuse Link Selection For Using Of Distribution Transformer Protection

The corresponding fuse is selected according to the time-current characteristics of the transformer,
usually according to the rated current of the transformer.

4gur_2tfv

yejz_xtbq

NOTE: Rated capacity of transformer ≤160kVA,the rated current of the selected fuse links should be 2-3 times of the full load  current of the transfor-mer, Rated capacity of transformer ≥160kVA,the rated current of the selected fuse links should be 1.5-2 times of the full load current of the transformer.

ax1c

Previous: 
Next: 

RELATED NEWS

content is empty!

PRODUCT

QUICK LINKS

CONTACT US

Email:  jonsonchai@chinahaivo.com

             sales@chinahaivo.com

             54442019@qq.com

Wechat:+86 13587716869

WhatsApp:+86 13587716869

Tel:       0086-577-62836929

              0086-577-62836926

              0086-13587716869

              0086-15957720101

Get Touch With Us

Contact us

If you have any questions, you can contact us through the form.

Copyright © 2020 Haivo Electrical Co.,Ltd Support  by  leadong.com   Sitemap  |  Privacy Policy